Rechercher
Français

Electronic Current-Transducer Type STWA4MH

Fabricant:

Ziehl

Numéro de pièce du fabricant:

S225570
Délai de livraison: 12 business days

AC Electronic current transformer, AC 0 - 60 A, with interface RS485

137,2 CAD
Réductions de prix - Plus vous achetez, plus vous économisez
Quantité
10+
20+
Prix
124,6 CAD
110,6 CAD
+ -
Spécifications des produits
Brand ZIEHL
Country of origin Germany
Rated supply voltage DC 24 V, 10,0 ... 30,0 V, <0,25 W
Frequency Range(Hz) 40...70
Ambient temperature range -20...+55 °C
Input current(mA) AC 0 ... 60 A, sinus shaped (RMS)
Resolution 1 mA
Applied standards UL/CSA

STWA4MH is a measuring transducer. It measures AC up to 60A and has an RS485 interface (Modbus RTU). The measured analog current value is made available as a digital signal and can be read by a PLC, an IPC or a master computer.

The conductor to be measured is passed through an opening (Ø 11 mm). In case of small currents, the sensitivity of the current transducer can be increased by looping through the current-carrying conductor several times, e.g. double looping doubles the sensitivity. The measuring range of the STWA4MH is reduced by multiple looping. To measure currents of any size, the STWA4MH is simply looped into the secondary circuit of a large current transformer with a secondary output of 5A (lead the cable through STWA4MH several times).

Application:
The STWA4MH enables the space-saving an cost-effective measurement of the actual value of an alternating current. Compared to transducers with analog output, the bus technology significantly  reduces the effort for the hardware (inputs) and the wiring. Applications are e.g. the recording of the current consumption of electrical motors in processing machines. Here the feed can be regulated depending on the load on the motor. Another example is the monitoring of consumers, e.g. heating elements, for failure.

 

Overview of Functions

  • Current measurement AC 0-60 A (RMS - Root Mean Square), resolution 1 mA
    • Actual value
    • Average over 200 ms
    • Average over 1 s
    • Measured values from the last 50 periods
  • Frequency measurement 40-70 Hz (sinus-shaped signals)
  • RS 485 interface (Modbus RTU)
  • Addressable for up to 246 participants
  • Baud rates 4800, 9600, 19200, 57600, 115200
  • Wiring effort minimized through bus technology
  • Supply voltage DC 24 V (10...30 V)
  • Connection via plug in spring type terminals
  • Lockable housing on mountin rail or screw fastening
  • Plug in current transformer (Ø 11 mm)
Entrez votre propre avis fermer
  • Un produit ne peut être commenté qu'après avoir été acheté
  • Seuls les utilisateurs enregistrés peuvent saisir des avis
  • Mauvais
  • Excellent
General Catalog

Data Sheet

Video
Request For Quote
Description

STWA4MH is a measuring transducer. It measures AC up to 60A and has an RS485 interface (Modbus RTU). The measured analog current value is made available as a digital signal and can be read by a PLC, an IPC or a master computer.

The conductor to be measured is passed through an opening (Ø 11 mm). In case of small currents, the sensitivity of the current transducer can be increased by looping through the current-carrying conductor several times, e.g. double looping doubles the sensitivity. The measuring range of the STWA4MH is reduced by multiple looping. To measure currents of any size, the STWA4MH is simply looped into the secondary circuit of a large current transformer with a secondary output of 5A (lead the cable through STWA4MH several times).

Application:
The STWA4MH enables the space-saving an cost-effective measurement of the actual value of an alternating current. Compared to transducers with analog output, the bus technology significantly  reduces the effort for the hardware (inputs) and the wiring. Applications are e.g. the recording of the current consumption of electrical motors in processing machines. Here the feed can be regulated depending on the load on the motor. Another example is the monitoring of consumers, e.g. heating elements, for failure.

 

Overview of Functions

  • Current measurement AC 0-60 A (RMS - Root Mean Square), resolution 1 mA
    • Actual value
    • Average over 200 ms
    • Average over 1 s
    • Measured values from the last 50 periods
  • Frequency measurement 40-70 Hz (sinus-shaped signals)
  • RS 485 interface (Modbus RTU)
  • Addressable for up to 246 participants
  • Baud rates 4800, 9600, 19200, 57600, 115200
  • Wiring effort minimized through bus technology
  • Supply voltage DC 24 V (10...30 V)
  • Connection via plug in spring type terminals
  • Lockable housing on mountin rail or screw fastening
  • Plug in current transformer (Ø 11 mm)
Spécifications des produits
Brand ZIEHL
Country of origin Germany
Rated supply voltage DC 24 V, 10,0 ... 30,0 V, <0,25 W
Frequency Range(Hz) 40...70
Ambient temperature range -20...+55 °C
Input current(mA) AC 0 ... 60 A, sinus shaped (RMS)
Resolution 1 mA
Applied standards UL/CSA
Tags des produits