Voltage Monitor for 3-Phase Networks Type SW31K 400v

Manufacturer:

Ziehl

Manufacturer part number:

S222272
Delivery date: 12 business days

Under voltage Relay for 3-phase networks, Housing type K for switch gear cabinet mount

149.8 CAD
PRICE BREAKS - Buy More, Save More
Quantity
10+
20+
Price
135.8 CAD
120.4 CAD
+ -
Products specifications
Brand ZIEHL
Country of origin Germany
Rated supply voltage AC 400V
Frequency Range(Hz) 50/ 60
Ambient temperature range -20...+55 °C
Protection housing/terminals IP 30 / IP20
Applied standards UL/CSA

Undervoltage monitor for threephase networks without N for monitoring on voltage failure. The voltage is being measured between phases and an artificial neutral point. At symmetrical decrease of the voltage to approx. 50% of the nominal value or in case of failure of a phase the integrated relay (1 change-over contact) releases with a delay ofapprox. 1s. With engines runningon on 2 phases, so much back voltage can be produced that the failure of a phase may be not detected. The SW31K is available for measuring voltages AC 400 V and AC 690 V. As supply voltage in the standard version AC 230 V is needed.

Application

  • Monitoring of three-phase networks on loss of a phase
  • monitoring of fuses
Write your own review Close Review Form
  • Product can be reviewed only after purchasing it
  • Only registered users can write reviews
  • Bad
  • Excellent
General Catalog

Data Sheet

Video
Request For Quote
Description

Undervoltage monitor for threephase networks without N for monitoring on voltage failure. The voltage is being measured between phases and an artificial neutral point. At symmetrical decrease of the voltage to approx. 50% of the nominal value or in case of failure of a phase the integrated relay (1 change-over contact) releases with a delay ofapprox. 1s. With engines runningon on 2 phases, so much back voltage can be produced that the failure of a phase may be not detected. The SW31K is available for measuring voltages AC 400 V and AC 690 V. As supply voltage in the standard version AC 230 V is needed.

Application

  • Monitoring of three-phase networks on loss of a phase
  • monitoring of fuses
Products specifications
Brand ZIEHL
Country of origin Germany
Rated supply voltage AC 400V
Frequency Range(Hz) 50/ 60
Ambient temperature range -20...+55 °C
Protection housing/terminals IP 30 / IP20
Applied standards UL/CSA
Product tags