Products specifications
Brand ZIEHL
Country of origin Germany
Rated supply voltage 3-phase, 400 V without N
Tolerance AC +20%...-30%
Output relays 2 change-over contacts (co), ca. 3 VA
Limit asymmetry adjustable 5...25 %
Limit undervoltage adjustable 70...95 %
Delay undervoltage/asymmetry adjustable 0,1...10 s
Protection housing/terminals IP 30 / IP20
Delay phase-loss (<60% Us) < 0,2 s
Pick-up delay after recovery of Us < 0,5 s
Delay K2 - K1 app. 100 ms

Phase-Sequence-Change Relays DRR20 measure the sequence of the phases and switch – if necessary the rotation of the field. At the output (connect relays K1 and K2 in series in this application) two contactors are connected. The contactor at the normally-open contact of K2 switches the phases 1:1without changing them, the second (atnormally-closed contact) changes 2 phases.

When switching on with phasesequence ok, relay K2 picks up. With wrong phase-sequence it remains released. After K2 has switched, K1 picks up. K1 also releases first. This makes sure, that no wrong contactor can be picked up under any condition. Additionally the DRR20 monitors the three phases for asymmetry and undervoltage. If the limits are exceeded, the K1 switches off (respectively doesn't pick up) and protects the connected motor from damage. The device can also be used as a monitor for undervoltage, asymmetry or phase-sequence.

Applications are machines and equipment that is operated at variable locations, e.g. at building sites. Pumps, compressors and vacuum-cleaners always run correctly and they are protected from damage by undervoltage or asymmetry.

*automatic change of wrong phase-sequence when connected falsely (2 contactors afforded)

*running backward of motors is avoided *

no switching on at asymmetry or undervoltage

*relay K2 picks up when phase-sequence is correct

*relay K1 picks up (after K2) when symmetry and voltage is correct

*3 LEDs for state of relays and errors

*measuring-voltage 3 AC 400 V

*limit asymmetry adjustable 5…25 %

*limit undervoltage adjustable 70…95 %

*alarm-delay adjustable 0,1…10 s (undervoltage and asymmetry)

*no supply-voltage required

Write your own review Close Review Form
  • Product can be reviewed only after purchasing it
  • Only registered users can write reviews
  • Bad
  • Excellent
General Catalog

Data Sheet

Video
Request For Quote
Description

Phase-Sequence-Change Relays DRR20 measure the sequence of the phases and switch – if necessary the rotation of the field. At the output (connect relays K1 and K2 in series in this application) two contactors are connected. The contactor at the normally-open contact of K2 switches the phases 1:1without changing them, the second (atnormally-closed contact) changes 2 phases.

When switching on with phasesequence ok, relay K2 picks up. With wrong phase-sequence it remains released. After K2 has switched, K1 picks up. K1 also releases first. This makes sure, that no wrong contactor can be picked up under any condition. Additionally the DRR20 monitors the three phases for asymmetry and undervoltage. If the limits are exceeded, the K1 switches off (respectively doesn't pick up) and protects the connected motor from damage. The device can also be used as a monitor for undervoltage, asymmetry or phase-sequence.

Applications are machines and equipment that is operated at variable locations, e.g. at building sites. Pumps, compressors and vacuum-cleaners always run correctly and they are protected from damage by undervoltage or asymmetry.

*automatic change of wrong phase-sequence when connected falsely (2 contactors afforded)

*running backward of motors is avoided *

no switching on at asymmetry or undervoltage

*relay K2 picks up when phase-sequence is correct

*relay K1 picks up (after K2) when symmetry and voltage is correct

*3 LEDs for state of relays and errors

*measuring-voltage 3 AC 400 V

*limit asymmetry adjustable 5…25 %

*limit undervoltage adjustable 70…95 %

*alarm-delay adjustable 0,1…10 s (undervoltage and asymmetry)

*no supply-voltage required

Products specifications
Brand ZIEHL
Country of origin Germany
Rated supply voltage 3-phase, 400 V without N
Tolerance AC +20%...-30%
Output relays 2 change-over contacts (co), ca. 3 VA
Limit asymmetry adjustable 5...25 %
Limit undervoltage adjustable 70...95 %
Delay undervoltage/asymmetry adjustable 0,1...10 s
Protection housing/terminals IP 30 / IP20
Delay phase-loss (<60% Us) < 0,2 s
Pick-up delay after recovery of Us < 0,5 s
Delay K2 - K1 app. 100 ms
Product tags