Search
English
You have no items in your shopping cart.

Measuring-Transducer Type MU1001K

Manufacturer:

Ziehl

Manufacturer part number:

T236006.1
Delivery date: 12 business days

Universal Measuring Transducer for DC voltage and DC current, isolation amplifier, scaleable

260.4 CAD
PRICE BREAKS - Buy More, Save More
Quantity
10+
20+
Price
235.2 CAD
208.6 CAD
+ -
Products specifications
Brand ZIEHL
Country of origin Germany
Rated supply voltage AC/DC 24 – 240 V 0/50…400 Hz < 3 W < 8 VA
Protection housing IP 40
Protection terminals IP 20
Tolerance DC DC 20,4 - 297 V
Resolution 11,6 Bit < 3,1 mV
Voltage output DC 0/2 – 10 V
Temperature factor < 0,01 % / K
Current output DC 0/4 – 20 mA
Applied standards UL/CSA

Universal Measuring-Transducers MU1001K can measure DC-signals up to 300 V. Inputs 60/150/300 mV measure direct current. Pre-set measuring-ranges can be selected by the user. More measuring-ranges (zero and full scale) can be easily scaled. The output-signals DC 0/2-10 V and 0/4-20 mA are insulated from measuring-input and supply-voltage.

With its universal power-supply AC/DC 24-240 V the measuring-transducer can be connected to all common supply-voltages.

Write your own review Close Review Form
  • Product can be reviewed only after purchasing it
  • Only registered users can write reviews
  • Bad
  • Excellent
General Catalog

Data Sheet

Video
Request For Quote
Description

Universal Measuring-Transducers MU1001K can measure DC-signals up to 300 V. Inputs 60/150/300 mV measure direct current. Pre-set measuring-ranges can be selected by the user. More measuring-ranges (zero and full scale) can be easily scaled. The output-signals DC 0/2-10 V and 0/4-20 mA are insulated from measuring-input and supply-voltage.

With its universal power-supply AC/DC 24-240 V the measuring-transducer can be connected to all common supply-voltages.

Products specifications
Brand ZIEHL
Country of origin Germany
Rated supply voltage AC/DC 24 – 240 V 0/50…400 Hz < 3 W < 8 VA
Protection housing IP 40
Protection terminals IP 20
Tolerance DC DC 20,4 - 297 V
Resolution 11,6 Bit < 3,1 mV
Voltage output DC 0/2 – 10 V
Temperature factor < 0,01 % / K
Current output DC 0/4 – 20 mA
Applied standards UL/CSA
Product tags